EXCEPTION to 160.2(b)1Bi: For heat recovery ventilators and energy recovery ventilators the location of the filters required by Section 160.2(b)1 may be downstream of a system thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component.
Systems specified in Section 160.2(b)1Ai shall be equipped with air filters that meet either Subsection a or b below:
Aface = Qfilter / Vface
Where:
Aface = air filter face area, the product of air filter nominal length x nominal width, ft2
Qfilter = design airflow rate for the air filter, ft3/min
Vface = air filter face velocity ≤ 150 ft/min
EXCEPTION to Section 160.2(b)2Aiia: The Energy Commission may approve continuous operation of central fan integrated ventilation systems pursuant to Section 10-109(h).
Total Required Ventilation Rate [ASHRAE 62.2:4.1.1].
Equation 160.2-B
Qtot = 0.03Afloor + 7.5(Nbr + 1)
WHERE:
Qtot = total required ventilation rate, cfm
Afloor = dwelling-unit floor area, ft2
Nbr = number of bedrooms (not to be less than 1)
When using Table 160.2-H for demonstrating compliance, the airflow rating shall be greater than or equal to the value required by Section 160.2(b)2Avi at a static pressure greater than or equal to 0.25 in. of water (62.5 Pa). When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with Section 160.2(b)2Avic2, a static pressure greater than or equal to 0.25 in. of water at the rating point shall not be required, and the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be applied to Table 160.2-H for determining compliance.
Use of Table 160.2-H is limited to ventilation systems that conform to all of the following three specifications:
EXCEPTION to Section 160.2(b)2Avif: Kitchen range hoods may be rated for sound at a static pressure determined at working speed as specified in HVI 916 Section 7.2.
EXCEPTION to Section 160.2(c)1A: For heat recovery ventilators and energy recovery ventilators the location of the filters required by Section 160.2(c)1A may be downstream of a system’s thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component.
EXCEPTION to Section 160.2(c)2Aiv: For ceilings that are increasing in height as distance from the opening is increased, the ceiling height shall be determined as the average height of the ceiling within 20 feet from the operable openings. [ASHRAE 62.1:6.4.1.4]
Vz = Ra x Az
Where:
Ra = Outdoor airflow rate required per unit area as determined from Table 160.2-B.
Az = Zone floor area is the net occupiable floor area of the ventilation zone in square feet.
Vz = Rp x Pz
Where:
Rp = 15 cubic feet per minute of outdoor airflow per person
Pz = The expected number of occupants. The expected number of occupants shall be the expected number specified by the building designer. For spaces with fixed seating, the expected number of occupants shall be determined in accordance with the California Building Code.
EXCEPTION to Section 160.2(c)3: Transfer air. The rate of outdoor air required by Section 160.2(c)3 may be provided with air transferred from other ventilated space if:
EXCEPTION 1 to Section 160.2(c)5A: Demand control ventilation. In intermittently occupied spaces that do not have processes or operations that generate dusts, fumes, mists, vapors or gases and are not provided with local exhaust ventilation (such as indoor operation of internal combustion engines or areas designated for unvented food service preparation), the rate of outdoor air may be reduced if the ventilation system serving the space is controlled by a demand control ventilation device complying with Section 160.2(c)5D or by an occupant sensor ventilation control device complying with Section 160.2(c)5E.
EXCEPTION 2 to Section 160.2(c)5A: Temporary reduction. The rate of outdoor air provided to a space may be reduced below the level required by Section 160.2(c) for up to 30 minutes at a time if the average rate for each hour is equal to or greater than the required ventilation rate.
EXCEPTION 1 to Section 160.2(c)5C: Where space exhaust is greater than the design ventilation rate specified in Section 160.2(c)3 minus 0.2 cfm per ft² of conditioned area.
EXCEPTION 2 to Section 160.2(c)5C: Spaces that have processes or operations that generate dusts, fumes, mists, vapors, or gases and are not provided with local exhaust ventilation, such as indoor operation of internal combustion engines or areas designated for unvented food service preparation, daycare sickrooms, science labs, barber shops or beauty and nail salons shall not install demand control ventilation.
EXCEPTION 3 to Section 160.2(c)5C: Spaces with an area of less than 150 square feet, or a design occupancy of less than 10 people as specified by Section 160.2(c)3.
EXCEPTION to Section 160.2(c)5Diii: The outdoor air ventilation rate is not required to be larger than the design outdoor air ventilation rate required by Section 160.2(c)3 regardless of CO2 concentration.
EXCEPTION to Section 160.2(c)8Bv: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 2 air shall not exceed 10% of the outdoor air intake flow.
EXCEPTION to Section 160.2(c)8Cii: When using any energy recovery device, recirculation from leakage, carryover, or transfer from the exhaust side of the energy recovery device is permitted. Recirculated Class 3 air shall not exceed 5 percent of the outdoor air intake flow.
|
TMY3
|
wsf
|
Weather Station
|
Latitude
|
Longitude
|
State
|
|
690150
|
0.50
|
Twentynine Palms
|
34.30
|
–116.17
|
California
|
|
722860
|
0.43
|
March AFB
|
33.90
|
–117.25
|
California
|
|
722868
|
0.45
|
Palm Springs Intl
|
33.83
|
–116.50
|
California
|
|
722869
|
0.42
|
Riverside Muni
|
33.95
|
–117.45
|
California
|
|
722880
|
0.39
|
Burbank–Glendale–Pasadena AP
|
34.20
|
–118.35
|
California
|
|
722885
|
0.39
|
Santa Monica Muni
|
34.02
|
–118.45
|
California
|
|
722886
|
0.39
|
Van Nuys Airport
|
34.22
|
–118.48
|
California
|
|
722895
|
0.55
|
Lompoc (AWOS)
|
34.67
|
–120.47
|
California
|
|
722897
|
0.51
|
San Luis Co Rgnl
|
35.23
|
–120.63
|
California
|
|
722899
|
0.45
|
Chino Airport
|
33.97
|
–117.63
|
California
|
|
722900
|
0.38
|
San Diego Lindbergh Field
|
32.73
|
–117.17
|
California
|
|
722903
|
0.39
|
San Diego/Montgomery
|
32.82
|
–117.13
|
California
|
|
722904
|
0.40
|
Chula Vista Brown Field NAAS
|
32.58
|
–116.98
|
California
|
|
722906
|
0.39
|
San Diego North Island NAS
|
32.70
|
–117.20
|
California
|
|
722926
|
0.40
|
Camp Pendleton MCAS
|
33.30
|
–117.35
|
California
|
|
722927
|
0.38
|
Carlsbad/Palomar
|
33.13
|
–117.28
|
California
|
|
722930
|
0.39
|
San Diego Miramar NAS
|
32.87
|
–117.13
|
California
|
|
722950
|
0.42
|
Los Angeles Intl Arpt
|
33.93
|
–118.40
|
California
|
|
722956
|
0.38
|
Jack Northrop Fld H
|
33.92
|
–118.33
|
California
|
|
722970
|
0.38
|
Long Beach Daugherty Fld
|
33.83
|
–118.17
|
California
|
|
722976
|
0.34
|
Fullerton Municipal
|
33.87
|
–117.98
|
California
|
|
722977
|
0.36
|
Santa Ana John Wayne AP
|
33.68
|
–117.87
|
California
|
|
723805
|
0.51
|
Needles Airport
|
34.77
|
–114.62
|
California
|
|
723810
|
0.59
|
Edwards AFB
|
34.90
|
–117.87
|
California
|
|
723815
|
0.58
|
Daggett Barstow–Daggett AP
|
34.85
|
–116.80
|
California
|
|
723816
|
0.62
|
Lancaster Gen Wm Fox Field
|
34.73
|
–118.22
|
California
|
|
723820
|
0.57
|
Palmdale Airport
|
34.63
|
–118.08
|
California
|
|
723830
|
0.68
|
Sandberg
|
34.75
|
–118.72
|
California
|
|
723840
|
0.43
|
Bakersfield Meadows Field
|
35.43
|
–119.05
|
California
|
|
723890
|
0.45
|
Fresno Yosemite Intl AP
|
36.78
|
–119.72
|
California
|
|
723895
|
0.42
|
Porterville (AWOS)
|
36.03
|
–119.07
|
California
|
|
723896
|
0.43
|
Visalia Muni (AWOS)
|
36.32
|
–119.40
|
California
|
|
723910
|
0.45
|
Point Mugu Nf
|
34.12
|
–119.12
|
California
|
|
723925
|
0.44
|
Santa Barbara Municipal AP
|
34.43
|
–119.85
|
California
|
|
723926
|
0.43
|
Camarillo (AWOS)
|
34.22
|
–119.08
|
California
|
|
723927
|
0.45
|
Oxnard Airport
|
34.20
|
–119.20
|
California
|
|
723940
|
0.52
|
Santa Maria Public Arpt
|
34.92
|
–120.47
|
California
|
|
723965
|
0.53
|
Paso Robles Municipal Arpt
|
35.67
|
–120.63
|
California
|
|
724800
|
0.55
|
Bishop Airport
|
37.37
|
–118.35
|
California
|
|
724815
|
0.46
|
Merced/Macready Fld
|
37.28
|
–120.52
|
California
|
|
724830
|
0.51
|
Sacramento Executive Arpt
|
38.50
|
–121.50
|
California
|
|
724837
|
0.45
|
Beale AFB
|
39.13
|
–121.43
|
California
|
|
724838
|
0.50
|
Yuba Co
|
39.10
|
–121.57
|
California
|
|
724839
|
0.51
|
Sacramento Metropolitan AP
|
38.70
|
–121.58
|
California
|
|
724915
|
0.49
|
Monterey Naf
|
36.60
|
–121.87
|
California
|
|
724917
|
0.54
|
Salinas Municipal AP
|
36.67
|
–121.60
|
California
|
|
724920
|
0.50
|
Stockton Metropolitan Arpt
|
37.90
|
–121.23
|
California
|
|
724926
|
0.47
|
Modesto City–County AP
|
37.63
|
–120.95
|
California
|
|
724927
|
0.53
|
Livermore Municipal
|
37.70
|
–121.82
|
California
|
|
724930
|
0.54
|
Oakland Metropolitan Arpt
|
37.72
|
–122.22
|
California
|
|
724935
|
0.47
|
Hayward Air Term
|
37.67
|
–122.12
|
California
|
|
724936
|
0.53
|
Concord–Buchanan Field
|
38.00
|
–122.05
|
California
|
|
724940
|
0.60
|
San Francisco Intl AP
|
37.62
|
–122.40
|
California
|
|
724945
|
0.48
|
San Jose Intl AP
|
37.37
|
–121.93
|
California
|
|
724955
|
0.55
|
Napa Co. Airport
|
38.22
|
–122.28
|
California
|
|
724957
|
0.49
|
Santa Rosa (AWOS)
|
38.52
|
–122.82
|
California
|
|
725845
|
0.44
|
Blue Canyon AP
|
39.30
|
–120.72
|
California
|
|
725846
|
0.66
|
Truckee–Tahoe
|
39.32
|
–120.13
|
California
|
|
725847
|
0.64
|
South Lake Tahoe
|
38.90
|
–120.00
|
California
|
|
725905
|
0.47
|
Ukiah Municipal AP
|
39.13
|
–123.20
|
California
|
|
725910
|
0.50
|
Red Bluff Municipal Arpt
|
40.15
|
–122.25
|
California
|
|
725920
|
0.47
|
Redding Municipal Arpt
|
40.52
|
–122.32
|
California
|
|
725945
|
0.56
|
Arcata Airport
|
40.98
|
–124.10
|
California
|
|
725946
|
0.60
|
Crescent City Faa Ai
|
41.78
|
–124.23
|
California
|
|
725955
|
0.55
|
Montague Siskiyou County AP
|
41.78
|
–122.47
|
California
|
|
725958
|
0.59
|
Alturas
|
41.50
|
–120.53
|
California
|
|
745090
|
0.45
|
Mountain View Moffett Fld NAS
|
37.40
|
–122.05
|
California
|
|
745160
|
0.67
|
Travis Field AFB
|
38.27
|
–121.93
|
California
|
|
746120
|
0.52
|
China Lake Naf
|
35.68
|
–117.68
|
California
|
|
747020
|
0.50
|
Lemoore Reeves NAS
|
36.33
|
–119.95
|
California
|
|
747185
|
0.46
|
Imperial
|
32.83
|
–115.58
|
California
|
|
747187
|
0.46
|
Palm Springs Thermal AP
|
33.63
|
–116.17
|
California
|
|
747188
|
0.48
|
Blythe Riverside Co Arpt
|
33.62
|
–114.72
|
California
|
|
Occupancy Category3
|
Exhaust Rate, cfm/unit
|
Exhaust Rate, cfm/ft2
|
Air Class
|
Notes
|
|
Copy, printing rooms
|
-
|
0.50
|
2
|
|
|
Janitor closets, trash rooms, recycling
|
-
|
1.00
|
3
|
|
|
Kitchenettes
|
-
|
0.30
|
2
|
|
|
Kitchens – commercial
|
-
|
0.70
|
2
|
|
|
Locker rooms for athletic or industrial facilities
|
-
|
0.50
|
2
|
|
|
All other locker rooms
|
-
|
0.25
|
2
|
|
|
Shower rooms
|
20/50
|
-
|
2
|
G, H
|
|
Parking garages
|
-
|
0.75
|
2
|
C
|
|
Pet shops (animal areas)
|
-
|
0.90
|
2
|
|
|
Soiled laundry storage rooms
|
-
|
1.00
|
3
|
F
|
|
Storage rooms, chemical
|
-
|
1.50
|
4
|
F
|
|
Toilets – private
|
25/50
|
-
|
2
|
E
|
|
Toilets – public
|
50/70
|
-
|
2..
|
D
|
|
General:
3 For spaces not included in this table, the spaces in Table 120.1-B shall apply. Notes: A –Reserved B –Reserved C – Exhaust shall not be required where two or more sides comprise walls that are at least 50% open to the outside. D – Rate is per water closet, urinal, or both. Provide the higher rate where periods of heavy use are expected to occur. The lower rate shall be permitted to be used otherwise. E – Rate is for a toilet room intended to be occupied by one person at a time. For continuous systems operation during hours of use, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. F – See other applicable standards for exhaust rate. G – For continuous system operation, the lower rate shall be permitted to be used. Otherwise the higher rate shall be used. H – Rate is per showerhead. |
||||
|
Description
|
Air Class
|
|
Commercial kitchen grease hoods
|
4
|
|
Commercial kitchen hoods other than grease
|
3
|
|
Hydraulic elevator machine room
|
2
|
Ratings According to Dwelling Unit Floor Area and Kitchen Range Fuel Type
Dwelling Unit Floor Area (ft2 ) | Hood Over Electric Range | Hood Over Natural Gas Range |
>1500 | 50% CE or 110 cfm | 70% CE or 180 cfm |
>1000 - 1500 | 50% CE or 110 cfm | 80% CE or 250 cfm |
750 - 1000 | 55% CE or 130 cfm | 85% CE or 280 cfm |
<750 | 65% CE or 160 cfm | 85% CE or 280 cfm |
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.